Multi turn lmp-s series of electric actuators

Technical parameters:
The temperature range is - 20 ℃ - + 60 ℃, - 30 ℃ - + 70 ℃, - 40 ℃ - + 80 ℃,
Extreme environment 0 ℃ - + 120 ℃ (lmtork split actuator can be used)

Share to:
Technical parameters:
The temperature range is - 20 ℃ - + 60 ℃, - 30 ℃ - + 70 ℃, - 40 ℃ - + 80 ℃,
Extreme environment 0 ℃ - + 120 ℃ (lmtork split actuator can be used)
Relative humidity 95% (70 ℃) (customizable)
Altitude: not higher than 2000m (customizable)
Protection grade: IP68
Explosion proof grade: Exd iict4
Motor working mode: s2-15min short time working mode, F-class insulation
S5 - intermittent cycle working system, the minimum load lasts for 10%, and the maximum working times is 1200C / h
Power supply: three-phase 380V AC 50 Hz, single-phase 220 V AC 50 Hz (specification below 250 nm)
Connection standard: jb2920 / iso5210 (customizable)
Cable inlet: 1 1 / 2 "NPT (one), 1" NPT (two) (customizable)
Main electrical parameters:
Power supply: three-phase 380V AC 50 Hz, single-phase 220 V AC 50 Hz (specification below 250 nm)
Contact capacity: 250VAC 5a, 30VDC 5A
Number of connections: 47
Cross section of signal conductor: ≤ 2.5mm2
Power wire cross section: ≤ 6 square mm
Switch input: input mode, passive contact voltage 24 VDC + / - 20%, current ≤ 10 Ma, pulse width greater than 100 ms, photoelectric isolation with reverse voltage protection
Switch output: output mode passive contact; capacity 250VAC 5a, 30VDC 5A
Set value input: range 4-20mA
Position feedback output: range 4-20mA, load capacity ≤ 500 ohm, linearity 0.3%
Control: deadband 0.1% - 9.9% adjustable